Ask ten people what starts an arcflash and you’ll hear everything from “it only happens above 600 V” to “PPE fixes the problem.” After twentyodd years crawling through switchrooms, I’ve learned that most of those answers are—well—half right at best. Let’s unpack the five myths you might run into the most and the engineering facts that push back on those myths. 

Myth1 “Arc flash is a medium/high voltage problem.” 

Reality: At 208V, an 80kA fault cleared in 0.20s still dumps around 10cal/cm² on the worker’s chest—well above Category2 limits. Voltage is just one variable; arcing current, clearing time, gap, and working distance call the shots. IEEE15842018 updated the arcingcurrent equations precisely because lowvoltage systems were underpredicted in the 2002 model. 

Myth2 “Brand new gear is practically arc flash proof.” 

Reality: New metal doesn’t stay new once it’s wired, leaned on, and neglected. A swapped feeder breaker or a larger utility transformer can double the available fault current overnight. NFPA70E2024 even added an informational note listing system changes—including transformer sizing—that invalidate your last study (Article130.5(G) note).  

Myth3 “If the breaker’s trip curve looks fast, I’m safe.” 

Reality: A time–current curve shows how a device reacts to boltedfault current. The arcing current is lower—sometimes low enough to ride the breaker’s longtime band and burn for 30+ cycles. IEEE1584 calls for calculating two arcingcurrent values (100% and 85%) and rerunning the protectivedevice model for each. Skip that step and you’re guessing.  

Myth4 “Dust and corrosion aren’t a big deal.” 

Reality: A dusty MCC is basically a resistor network waiting to conduct. Surface contamination lowers breakdown voltage, letting an arc jump at normal operating voltage that would otherwise be harmless. NFPA70E places equipment condition right next to design when assessing likelihood of an event (Table130.5(C)).  

Myth5 “PPE is the main line of defense.” 

Reality: PPE is the last line. Table130.5(G) in NFPA70E2024 literally appears after the riskassessment steps that ask whether you can engineer the energy down first. If your incident energy is 40cal/cm² and you simply issue a Category4 suit, you’ve accepted a firesuit budget and the downtime that comes with it. There’s usually a smarter fix: currentlimiting fuses, maintenance settings, relay setting audits, remote racking, or just cleaning the gear.  

Why this isn’t just academic 

  • Human cost Arc temperatures reach 35,000°F; survivability drops to nearzero above 12cal/cm². 
  • Operational cost OSHA fines, lost production, litigation—one event can blow past $1M in hours. 
  • Compliance Labels must now survive the environment they live in (70E130.5(H)), and studies must be updated when “system modifications” occur. Staying current isn’t optional.  

If your last arcflash label predates the 2018 IEEE model—or if you’ve added a single piece of gear since then—your numbers might be wishful. And no, a fresh set of gloves won’t fix it. 

 

Download our Arc Flash Protection Reference Guide